Installer reference guide / Mono tank integrated type 122
Key Option
AE080BXYD**, AE120BXYD**, AE140BXYD**
Option SEG1 SEG2 SEG3 SEG4 Function of the option Remarks
Current restriction
rate
0 0
0 0 100% (Factory default)
When restriction option is set,
cooling and heating performance
may decrease.
0 1 95%
0 2 90%
0 3 85%
0 4 80%
0 5 75%
0 6 70%
0 7 65%
0 8 60%
0 9 55%
1 0 50%
1 1 No restriction
Defrost operation
0 1
0 0 Basic
-
0 1 Option
Fan speed correction
for outdoor unit
0 2
0 0 Basic
-
0 1 Option
Quiet mode
0 3
0 0 Low noise (Basic) -
0 1 Level1 -
0 2 Level2 -
0 3 Level3 -
Channel address
0 4
A U
Automatic setting
(Factory default)
Address for classifying the product
from upper level controller
0~15
Manual setting for
channel 0~15
Snow accumulation
prevention control
0 5
0 0
Enabled (Factory
default)
During snow accumulation, the
fan may spin even when the unit is
not in operation.
0 1 Disabled
Base Heater
0 6
0 0 Disabled
-
0 1
Enabled (Factory default)
Operation mode
0 7
0 0
Heat pump (Factory
default)
-
0 1 Cooling only (Disabled)
0 2 Heating only
Energy saving mode
0 8
0 0
Disabled (Factory
default)
Cannot be used in combination
with centralized control or Snow
Accumulation Prevention mode.
0 1 Enabled