Installer reference guide / Mono tank integrated type 136
Menu 30** : DHW code
User’s options for DHW tank heating
0
Please enter your PASSWORD
Service Mode
Service Mode
Service Timer
Quiet Mode Automatic Time
Indoor Zone Option
Connection Information
Device Information
Reset All Service Modes
Power Master Reset
ODU K3 Reset
Field Setting Value
Self-Test Mode
Indoor Unit Option
Field Setting Value
10** | Remote Controller
20** | Water Law
30** | DHW
40** | Heat
50** | Others
Simple Setting
FSV Upload/Download
10** | Remote Controller
101* | Water Out Temp. for Cool
102* | Room Temp. for Cool
103* | Water Out Temp. for Heat
104* | Room Temp. for Heat
105* | DHW Tank Temp.
0
Please enter your PASSWORD
Service Mode
Service Mode
Service Timer
Quiet Mode Automatic Time
Indoor Zone Option
Connection Information
Device Information
Reset All Service Modes
Power Master Reset
ODU K3 Reset
Field Setting Value
Self-Test Mode
Indoor Unit Option
Field Setting Value
10** | Remote Controller
20** | Water Law
30** | DHW
40** | Heat
50** | Others
Simple Setting
FSV Upload/Download
20** | Water Law
201* | Outdoor Temp. for Water Law
202* | Water Out Temp. for WL1 Heat
203* | Water Out Temp. for WL2 Heat
204* | Heating Water Law for Auto Mode
205* | Outdoor Temp. for Water Law
206* | Water Out Temp. for WL1 Cool
207* | Water Out Temp. for WL2 Cool
0
Please enter your PASSWORD
Service Mode
Energy Generation Energy Consumption
Service Mode
Service Timer
Quiet Mode Automatic Time
Indoor Zone Option
Connection Information
Device Information
Reset All Service Modes
Power Master Reset
ODU K3 Reset
Field Setting Value
Self-Test Mode
Indoor Unit Option
Field Setting Value
10** | Remote Controller
20** | Water Law
30** | DHW
40** | Heat
50** | Others
Simple Setting
FSV Upload/Download
30** | DHW
301* | Domestic Hot Water Tank
302* | Heat Pump
303* | Booster Heat
304* | Disinfection
305* | Forced DHW Operation
306* | Solar Panel/DHW Thermostat
307* | Direction of 3Way Valve
308* | Energy Metering
0
Please enter your PASSWORD
Service Mode
Service Mode
Service Timer
Quiet Mode Automatic Time
Indoor Zone Option
Connection Information
Device Information
Reset All Service Modes
Power Master Reset
ODU K3 Reset
Field Setting Value
Self-Test Mode
Indoor Unit Option
Field Setting Value
10** | Remote Controller
20** | Water Law
30** | DHW
40** | Heat
50** | Others
Simple Setting
FSV Upload/Download
50** | Others
501* | Outing
502* | DHW Saving
503* | TDM Variable (TDM Product only)
504* | Power Peak Control
505* | Frequency Ratio Control
506* | Heat/DHW Capa. Ratio
508* | PV Control
509* | Smart Grid Control
0
Please enter your PASSWORD
Service Mode
Service Mode
Service Timer
Quiet Mode Automatic Time
Indoor Zone Option
Connection Information
Device Information
Reset All Service Modes
Power Master Reset
ODU K3 Reset
Field Setting Value
Self-Test Mode
Indoor Unit Option
Field Setting Value
10** | Remote Controller
20** | Water Law
30** | DHW
40** | Heat
50** | Others
Simple Setting
FSV Upload/Download
40** | Heat
401* | Heat Pump
402* | Backup Heater
403* | Backup Boiler
404* | Mixing Valve
405* | Inverter Pump
406* | Zone Control
2019
Generation 1000hr
60
Hr
40
20
0
2019
Usage 500kWh | Target 500kWh
60
kWh
40
20
0
Jan. Feb. Mar. A pr. May. Jun. Jul. Aug. Sep. Oct. Nov. (month)Jan. Feb. Ma r. Apr. May. Jun. Jul. Aug. Sep. Oct. Nov. (month)
Main Menu
(FSV)
Sub Menu Function Description FSV Step Unit Default Min. Max.
DHW
FSV 30**
DHW Application 3011 - - 1(Yes) 0 2
DWH option consist of following FSV
#3011 : DHW Application
The FSV #3011 in the wired remote controller should be set to 1 or 2 to use DHW function. Determined by #3011
when DHW operation is first run in combination operation.
: If FSV #3011 is set to 1, the DHW operation starts based on the thermo on temperature, but stops at thermo off
temperature.
: If FSV #3011 is set to 2, the DHW operation starts, but stops based on the thermo off temperature.


turns on if FSV #3011 is set to 2.)
FSV #3011: 1 -
when T
HP ON
< Ttank < T
HP OFF

HP ON
: Themo on
T
tank
T
HP OFF
T
HP ON

Thermo Off
Thermo On
Dotted line : Thermo off line
Solid line : Thermo on line
T
tank
: DHW tank temperature
T
HP ON
: Temperature for start (Heat Pump On)
T
HP OFF
: Temperature for stop (Heat Pump Off)
FSV #3011: 2 -
T
HP ON
< Ttank < T
HP OFF
, according to the previous thermo on/off control
T
tank
T
HP OFF
T
HP ON

Thermo OffThermo Off
Thermo On
Thermo On