Installer reference guide / Mono tank integrated type 140
4) Periodical Disinfection heating of water tank (#304*)
Main Menu
(FSV)
Sub Menu Function Description FSV Step Unit Default Min. Max.
DHW
FSV 30**
Disinfection
Application 3041 - - 1 (On) 0 (Off) 1
Interval 3042 1 day Fri (5) Sun (0) All (7)
Start Time 3043 1 o'clock 23 0 23
Target Temp. 3044 5 70 40 70
Duration 3045 5 min 10 5 60
Max time 3046 1 hour 8 1 24
#3043 : Start time for disinfection (0~24hr)
#3044 : Target temp.for disinfection
#3045 : Time duration which satisfy the target temp. for
disinfection
#3044
#3045#3042
#3043
5) Forced DHW operation (#305*)
Main Menu
(FSV)
Sub Menu Function Description FSV Step Unit Default Min. Max.
DHW
FSV 30**
Forced DHW
Operation
Timer OFF Function 3051 - - 0 (No) 0 1 (Yes)
Time Duration 3052 1 (x10)min 6 3 30
• Forced DHW mode shall be working depending on timer setting.
• #3051 : Set whether to use a timer for forced DHW function.
• #3052 : Set time for forced DHW operation.