78 S&C Instruction Sheet 461-509
NOTICE
A guide to pairing your TripSaver II recloser with the communications gateway can
also be found in S&C Instruction sheet 461-521, “TripSaver® II Cutout-Mounted
Recloser, Outdoor Distribution (15 kV and 25 kV): TripSaver® II Communications
via Gateway Pairing Quickstart Guide.”
DANGER
The TripSaver II Cutout-Mounted Recloser MUST be de-energized and removed
from the utility pole before attaching the “corded” power module (power module with
ac adapter and extension cord) to the base of the TripSaverII recloser. The corded
power module is ONLY intended to be used for setup and data collection when the
TripSaver II recloser is de-energized and removed from the utility pole. Failure to
remove the TripSaverII recloser from the utility pole before connecting the corded
power module can cause arcing, burns, electric shock, and death.
With the introduction of TripSaver II Cutout-Mounted Recloser rmware version 1.8 or
1.9, the TripSaver II recloser can be paired with a communications gateway at the users
service center using the power module from the service center conguration kit and the
S&C Magnet Tool. S&C recommends commissioning (pairing) TripSaver II reclosers
with the communications gateway one at a time. This will ensure each recloser is fully
connected to the communications gateway before pairing the next recloser. Pairing the
reclosers one at a time is the fastest method to pair a TripSaver II recloser and a com-
munications gateway. TripSaver II reclosers must be furnished with the Extended Open
Interval option, which allows up to a 30-second open interval between reclose operations.
To pair a TripSaver II recloser in the service center:
STEP 1. Using a PC loaded with Service Center Conguration Software, the corded
power module, a USB transceiver, and TripSaver II Service Center
Conguration Software, set the TripSaver II recloser loaded with rmware
version 1.8 or 1.9 to Gateway mode. Instructions for setting the recloser to
Gateway mode can be found in the “Communications Settings Menu” section
of S&C Instruction Sheet 461-504, “TripSaver® II Cutout-Mounted Recloser,
Outdoor Distribution (15 kV and 25 kV): For Overhead Distribution Systems:
Protection Setup Using Service Center Conguration Kit.”
STEP 2. Disconnect from the service center conguration software and remove the
USB transceiver from the PC. With the power module still connected to the
TripSaver II recloser, attach the magnet tools magnet to the green S&C logo
sticker on the side of the TripSaver II recloser. More information on using the
Magnet Tool can be found in S&C Instruction Sheet 461-507, “TripSaver® II
Cutout-Mounted Recloser, Outdoor Distribution (15 kV and 25 kV): Operation
Manual Enabling Pole-Top Communications Via the Magnet Tool.” This will
turn on the TripSaver II recloser’s wireless communications.
Service Center Pairing
a TripSaverII Recloser
with Firmware Version
1.8 or 1.9
Commissioning (Pairing) a TripSaver II Recloser for Use with
the Communications Gateway