80 S&C Instruction Sheet 461-509
as described in S&C Instruction Sheet 461-502, “TripSaver® II Cutout-Mounted
Recloser, Outdoor Distribution (15 kV and 25 kV): Installation and Operation,”
and power it via line current. Install the communications gateway no more
than 30 feet (9.1 m) from the TripSaver II recloser(s) to be paired. Connect the
communications gateway to ac power.
STEP 3. Connect to the communications gateway with a PC as described in the
“Software User’s Guide” section on page 19. In the Device Management
screen, click on the Add TripSaver II button. Fill in the Transceiver ID
and TripSaver II Device Name (if desired), and click on the OK button.
Note: The device name can be anything but is usually a description of where
the TripSaver II recloser is installed.
When the TripSaver II recloser has been successfully paired, the device
will appear in the device listing in the device panel. Periodically refresh
the communications gateway’s TripSaver II Device Management screen
using the browser’s Refresh button. The TripSaver II recloser will be listed
as “connected” when pairing is complete. The pairing process could take
approximately 15 minutes. If the TripSaver II recloser does not pair, see the
Troubleshooting” section on page 81.
Commissioning (Pairing) a TripSaver II Recloser for Use with
the Communications Gateway