29
Table 5-5 User Assignable Registers
Register Register contents Type R/W Range
0x8000 Assigned register #0
1
1
1
0x8001 Assigned register #1
1
1
1
… ... ...
0x8077 Assigned register #119
1
1
1
1
depends on the mapped register
Table 5-6 User Assignable Register Map
Register Register contents Type R/W Range
0x8100 Mapped address for register 0x8000 UINT16 R/W 0x0000 - 0xFFFF
0x8101 Mapped address for register 0x8001 UINT16 R/W 0x0000 - 0xFFFF
... ... ...
0x8177 Mapped address for register 0x8077 UINT16 R/W 0x0000 - 0xFFFF
To build your own register map, write to map registers (0x8100 to 0x8177) the actual addresses you want to read
from or write to via the assignable area (0x8000 to 0x8077). For example, if you want to read registers 0x0C00
(real-time voltage of phase A) and 0x1700 (kWh import) via registers 0x8000-0x8001, do the following:
- write 0x0C00 to register 0x8100
- write 0x1700 to register 0x8101
Reading from registers 0x8000-0x8001 will return the voltage reading in register 0x8000, and the kWh reading in
register 0x8001.