A01350693 Rev:P ECO: 7476 Date: 04/14/08 10
Each Exit Panel will require a 110/220/230VAC duplex outlet specific to regional or country options (minimum 2 Amp) within ten
cable feet of the intended installation location. The use of emergency power circuits is highly recommended due to possible facility
power failures.
NOTES:
•
Power Wire: 14/2 stranded, unshielded (SCP Part # C60008473). Power wire is a UL requirement. Failure to
use this wire removes the UL listing.
• Power Supply: SCP Part # C40006008. For overseas 230VA Power Supply refer to Appendix B.
• Do not connect to a receptacle controlled by a switch.
•
Do not extend the power supply cord provided. The maximum distance the duplex outlet should be from
the Exit Panel is ten cable feet.
SECTION 3 POWER AND GROUNDING REQUIREMENTS