A01350693 Rev:P ECO: 7476 Date: 04/14/08 36
Delayed Egress Release Time
Each Exit Panel controlling an electromagnetic lock has a required time period for pressure applied to a door to release the locking
feature as required by NFPA 101. Refer to the NFPA 101 Life Safety Code or your local fire Marshall/safety inspector for guidance
on local requirements.
Delayed Egress Release Time Factory Default 15 seconds
To change the release time from 15 to 30 seconds, follow the three listed steps without pausing for greater than one second between
keystrokes.
1. Enter *567 or the currently programmed secondary code
2. Enter *9876543217#030
3. Multiple confirmation beeps = change accepted
4. Single confirmation beep = change not accepted
To change the release time from 30 to 15 seconds, follow the three listed steps without pausing for greater than one second between
keystrokes
.
1. Enter *567 or currently programmed secondary code
2. Enter *9876543217#015
3. Multiple confirmation beeps = change accepted
4. Single confirmation beep = change not accepted
Egress Activation for Nuisance Silent Default disabled
Currently a beeping will sound for the first 3 seconds when there is pressure applied to the door. With the Nuisance Silent
Feature enabled, it will silence the 3 second nuisance sound and will activate the egress process.
To enable Nuisance Silent enter *567*9876543217#777
To disable Nuisance Silent enter *567*9876543217#707
Delayed Egress Activation Time
Each Exit Panel controlling an electromagnetic lock has a required time period for pressure applied to a door to activate the delayed
egress release feature as required by NFPA 101. Refer to the NFPA 101 Life Safety Code or your local fire Marshall/safety inspector
for guidance on local requirements. This feature allows you to modify the time necessary to apply the constant even pressure upon
the door to activate the delayed egress alarm mode. The four options below are 3 sec., 2 sec., 1 sec., and 0 sec. Changing the
activation time from factory default should be done only after permission is granted by the local Authority having jurisdiction.
Delayed Egress Activation Time Factory Default 3 Seconds
To change the activation time to 3 seconds, follow the three listed steps without pausing for greater than one second between
keystrokes.
1. Enter *567 or the currently programmed secondary code
2. Enter *9876543217#753
3. Three confirmation beep = change accepted
4. No confirmation beep = change not accepted
SECTION 10 PROGRAMMING