A01350693 Rev:P ECO: 7476 Date: 04/14/08 37
To change the activation time to 2 seconds, follow the three listed steps without pausing for greater than one second between
keystrokes.
1. Enter *567 or the currently programmed secondary code
2. Enter *9876543217#852
3. Two confirmation beeps = change accepted
4. No confirmation beep = change not accepted
To change the activation time to 1 second, follow the three listed steps without pausing for greater than one second between
keystrokes.
1. Enter*567 or the currently programmed secondary code
2. Enter *9876543217#951
3. One confirmation beeps = change accepted
4. No confirmation beep = change not accepted
To change the activation time to 0 seconds, follow the three listed steps without pausing for greater than one second between
keystrokes.
1. Enter *567 or the currently programmed secondary code
2. Enter *9876543217#580
3. Four confirmation beeps = change accepted
4. No confirmation beep = change not accepted
Latching Delayed Egress
Each Exit Panel controlling an electromagnetic lock has a required time period for pressure applied to a door to release the locking
feature as required by NFPA 101. This feature, when enabled, allows the door to remain unlocked once the delayed egress feature is
activated until an authorized reset code is entered into the Exit Panel.
Latching Delayed Egress Factory Default Disabled
To enable the latching delayed egress feature, follow the three listed steps without pausing for greater than one second between
keystrokes.
1. Enter *567 or the currently programmed secondary code
2. Enter *9876543217#999
3. Four confirmation beeps = change accepted
To disable the latching delayed egress feature, follow the three listed steps without pausing for greater than one second between
keystrokes.
1. Enter *567 or the currently programmed secondary code
2. Enter *9876543217#909
3. Three confirmation beeps = change accepted
One Second Irreversible Latching Delayed Egress
The 135DE Exit Panel has a special one second irreversible latching delayed egress feature. When enabled, in the presence of a
transmitter and the activation of the nuisance alarm, the delayed egress cycle will unlock the door and keep it unlocked with an
audible alarm until a reset code is entered. Once the delayed egress cycle has been activated, the door will not reset itself even if the
transmitter is taken out of the detection range.
One Second Irreversible Latching Delayed Egress Factory Default Disabled
To enable the one second irreversible latching delayed egress feature, follow the three listed steps without pausing for greater than
one second between keystrokes.
1. Enter *567 or the currently programmed secondary code
2. Enter *9876543217#888
3. Four confirmation beeps = change accepted
SECTION 10 PROGRAMMING