A01350693 Rev:P ECO: 7476 Date: 04/14/08 38
To disable the one second irreversible latching delayed egress feature follow the three listed steps without pausing for greater than
one second between keystrokes.
1. Enter *567 or the currently programmed secondary code
2. Enter *9876543217#808
3. Three confirmation beeps = change accepted
Fire Alarm Input Selection
Fire Alarm Input
Factory Default Normally Open
To change to input of the Fire alarm relay enter the following:
Normally Closed fire alarm contact active
1. Enter *567 or the currently programmed secondary code
2. Enter *9876543216#000
3. Two confirmation beeps = change accepted
4. One confirmation beep = change not accepted
Normally Open fire alarm contact active
1. Enter *567 or the currently programmed secondary code
2. Enter *9876543216#001
3. Three confirmation beeps = change accepted
4. One confirmation beep = change not accepted
Latching Fire Alarm
To Enable the Latching Fire Alarm
1. Enter *567*9876543216 #999
2. Four confirmation beeps = change accepted
3. One confirmation beep = change not accepted
To Disable the Latching Fire Alarm
1. Enter *567*9876543216 #909
2. Five confirmation beeps = change accepted
3. One confirmation beep = change not accepted
Life Safety Lock
You can lock all Life Safety 101 features. This will lock the delayed egress and fire alarm settings. This feature is NON
REVERSIBLE and cannot be undone by initializing the panel. Make sure the Life Safety 101 features are correct and meet
your local authorities requirements before locking the feature .To undo this feature the panel will have to be sent back to
Secure Care Products, Inc. to be reprogrammed.
To LOCK Life Safety Features: Enter *309*9876543219
Panel ID Code
Each Exit Panel requires its own unique ID code for reporting purposes on the CAN bus (if used). Any event message will
be transmitted on the CAN bus beginning with the Exit Panel ID code followed by the message string. The Exit Panel ID is
also supervised by the XIU for power.
Panel ID Code
Factory Default 255
To change the panel ID code, follow the three listed steps without pausing for greater than one second between keystrokes.
1. Enter *567 or the currently programmed Secondary code
2. Enter *9876543213#XXX (XXX = three digit number)
3. Multiple confirmation beeps = change accepted
4. Single confirmation beep = change declined