Trip IL1/L2/L3, Trip IPh, Trip IG (*)
wiProtGeneral_Y03
Prot . Trip IL1
34
I> . Trip IL1
I>>> . Trip IL1
1
18
Prot . Active
&
I>> . Trip IL1
1
Prot . Trip IPh
Prot . Trip IG
37
Ipeak> . Trip IL1
35
I> . Trip IL2
I>>> . Trip IL2
1
I>> . Trip IL2
38
Ipeak> . Trip IL2
36
I> . Trip IL3
I>>> . Trip IL3
1
I>> . Trip IL3
39
Ipeak> . Trip IL3
Prot . Trip IL2
&
Prot . Trip IL3
&
37
IG> . Trip
1 &
IG>> . Trip
51
Prot . Trip
ThR . Trip
21
I2/I1> . Trip
21
21
SOTF . Trip
ExP[1] . Trip
21
1
Prot . Trip Ext.
ExP[2] . Trip (**)
1
I2> . Trip
21
Fig. 42: Phase-selective General Trip signals and the respective collective signals.
(*)
All trip signals, including the phase-selective ones, are issued only by protection functions
that are set as »De󰅰nition« = “Trip”. (See also ╚═▷ “De󰊟nition (“Alarm ↔ Trip”) of a
Protection Function.) This is not shown explicitly in the diagram.
(**) A second »ExP« instance is available only on WIC1 variants with two Digital Inputs. (See
order options.)
127WIC1WIC1-1.0-EN-MAN
4 Protective Elements
4.1.1.2 Phase-Selective Signals, Collective Signals

Table of Contents

Other manuals for Seg WI Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Seg WI Series and is the answer not in the manual?

Seg WI Series Specifications

General IconGeneral
BrandSeg
ModelWI Series
CategoryRelays
LanguageEnglish

Related product manuals