10.4.3
Parameter Settings
Description Information Corrective Action
All settings are locked against
changes in Smart view.
This is probably not an error,
but due to the parameter
setting [Device planning / WIC1
+ DiggiMEC] »Prot . Settings
valid« = “Switches”.
Set »Prot . Settings valid« = “Software”
to enable a conguration via DiggiMEC
and/or Smart view.
(Be aware, however, that DIP/Hex
switches are ignored by then. See also
╚═▷ “Validity of the DIP-/HEX-Switches”.)
Settings via DIP/HEX switches are
not possible anymore.
This is probably not an error,
but due to the parameter
setting [Device planning / WIC1
+ DiggiMEC] »Prot . Settings
valid« = “Software”.
The DIP/HEX switches are taken into
account again only after a reset
to factory defaults. This is achieved
by the direct command [Service /
General] »Factory Reset«.
(See also ╚═▷ “2.12 Reset to Factory
Defaults”.)
242 WIC1 WIC1-1.0-EN-MAN
10 Troubleshooting
10.4.3 Parameter Settings