EasyManuals Logo

Seg WI Series User Manual

Seg WI Series
337 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #243 background imageLoading...
Page #243 background image
10.4.4
Protection and Control
Description Information Corrective Action
Problem with current measurement. The measured values of current
show a big ó°…±uctuation.
Adjust [Field Para / General
Settings] »f« to the connected grid
frequency (50 Hz or 60 Hz).
Binary outputs do not react. The contacts of the binary outputs
do not open or close. This
can be checked by simulating
a fault and checking the
binary output contacts with
measurement equipment.
Check the following issues:
• Has the DiggiMEC been correctly•
set within the WIC1 settings?
(Check menu branches [Device
planning / WIC1 + DiggiMEC] and
[Device Para / DiggiMEC].)
• Acknowledge the binary outputs, if•
applicable.
•
Is the status of the binary output
•
forced to a dedicated value? (The
binary output can be overwritten
for commissioning purpose, see
menu branch [Service / Test (Prot
inhibit)].)
•
Is the required protection function
•
active?
• Is overall protection active?•
•
Are the ó°ŠŸeld parameters set
•
correctly (CT ratio etc.)?
• Are the protection parameters set•
correctly (trip value, trip time)?
• Is the assigned protection function•
blocked?
•
Is the wiring correct?
•
243WIC1WIC1-1.0-EN-MAN
10 Troubleshooting
10.4.4 Protection and Control

Table of Contents

Other manuals for Seg WI Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Seg WI Series and is the answer not in the manual?

Seg WI Series Specifications

General IconGeneral
BrandSeg
ModelWI Series
CategoryRelays
LanguageEnglish

Related product manuals