3.7.1
Self-Supervision Contact for the WIC1‑4
Side View
X4
X5
COM / L
L+
Power Supply
X4-1
X4-2
X4-3
X4-4
X4-5
X4-6
X4-7
X4-8
+
+
+
+
+
PE
11
12
14
A2
A1
Self-Supervision Contact
Output:
trip coil
WIC1-4_ZSR
Fig. 30:
Connecting an external self-supervision contact.
An externally supplied WIC1‑4 allows for connecting an output relay that operates as a
Healthy” / self-supervision contact. (See diagram.)
1. ▷
The output relay must ful󰊟ll the speci󰊟cations in ╚═▷ “9.1.8.3 Relay Ouput (WIC1‑4)”.
2. ▷
The operating mode of the “Out+/−” output must be set via software parameter as
follows:
[Device Para / WIC1 / Output] »Prot . Out. Mode« = “Syst. O.K. & Ext.Suppl.”
(There is a special device-internal “Healthy” signal, that is used particularly for this purpose,
see also the diagram ╚═▷ Fig. 40 in ╚═▷ “4.1.1.1 Trip Pulse and WIC1 LEDs”. With the setting
above, this signal gets – internally and invisibly – assigned to the “Out+/−” output.)
89WIC1WIC1-1.0-EN-MAN
3 Hardware
3.7.1 Self-Supervision Contact for the WIC1‑4