4.1.2
Force Trip Command
For commissioning or testing purposes, the user can initiate a trip command manually via
[Service / Prot] »Prot . Force Trip Cmd«.
See also the function diagram, ╚═▷ Fig. 39.
But note that if the WIC1 is supplied only via USB then the voltage of the trip pulse
might be too low to actually trigger the breaker. See also ╚═▷ “2.3 Supply of a WIC1” and
“Troubleshooting: System-LED is O󰊞”.
128 WIC1 WIC1-1.0-EN-MAN
4 Protective Elements
4.1.2 Force Trip Command