9.3 Technical Data – DiggiMEC
NOTICE!
Use copper conductors only, 75°C.
Conductor size ≤ AWG 14 [2.5 mm²].
NOTICE!
Use an Ethernet cable CAT 3 (or better) with shielding for the connection between WIC1
and DiggiMEC. Crossover cables must not be used!
9.3.1
Climatic and Environmental Data
Storage Temperature: −30°C to +80°C (−22°F to 176°F)
Operating Temperature: −20°C to +60°C (−4°F to 140°F)
Permissible Humidity at Ann.
Average:
<75% rel. (on 56 days up to 95% rel.)
Permissible Installation
Altitude:
≤ 2000 m (6561.67 ft) above sea level
Vibration and continuous vibration test: 1 / 2 gn
DIN EN 60255-21-1 [05/96]
Class 2
Shock and continuous shock test: 10 / 20 gn
DIN EN 60255-21-2 [05/96]
Class 2
Earthquake test: 2 gn
DIN EN 60255-21-3 [05/96]
Class 2
9.3.2
Housing
Housing (Height / Width /
Depth):
53 mm / 102 mm / 55,8 mm
(see also dimension drawings in ╚═▷ “3.2.2 DiggiMEC Dimension
Drawings”)