11.2.2.2.7 RXIDG
»Char« = RXIDG
t / s
IG / IG> (multiples of pickup)
tChar=
wiEDOC_Z13
1 10 100
0.01
0.1
1
10
0.05
0.1
0.2
0.3
0.4
0.5
0.6
0.7
0.8
0.9
1.0
Fig. 100: RXIDG: trip delay, IG > I
G>
.
See ╚═▷ “Explanation for All Characteristics (IG>, IG>>)” and ╚═▷ “11.2.2.2 Inverse-Time
Characteristics (IG>, IG>>)” for details.
Reset Delay
The reset modes “instantaneous” or “de󰊟nite time” are available. For this characteristic,
there is no reset mode with dynamic reset delay.
Trip Delay
If IG> < IG, the trip delay is de󰊟ned by this equation, but only under the condition that the
resulting trip delay holds t > t
Dyn.Lim.
with t
Dyn.Lim.
= 0.02 s.
In other words, the trip delay t is always at least t
Dyn.Lim.
= 0.02 s.