4
Installation notes
Mechanical installation
Manual – MOVI‑C
®
CONTROLLER progressiveUHX65A
19
4.2 Mechanical installation
CAUTION
Risk of injury to persons and damage to property.
Never install defective or damaged MOVI-C
®
CONTROLLERs.
Before installation, check the device for external damage. Replace any damaged
device.
4.2.1 Minimum clearance and mounting position
MOVI‑C
®
CONTROLLER is installed in the control cabinet. Observe the following for
installation:
Install the device with the provided carrier plate to the metal bare back of the con-
trol cabinet.
To ensure unobstructed cooling of the MOVI-C
®
CONTROLLER, leave a minimum
clearance of 100mm above and below the device's housing as well as 20mm to
the right and left. Make sure air circulation in the clearance is not impaired by
cables or other installation equipment. The preferred mounting position is left of
the axis system.
Ensure unobstructed cooling air supply and make sure that the
MOVI‑C
®
CONTROLLER is not exposed to the warm exhaust air from other
devices.
Only install the device vertically. Do not install the devices horizontally, tilted or up-
side down.