5 Startup
5.1 Configuration of the EtherCAT
®
/SBus
PLUS
stations
Configurati
on of the
EtherCAT®/
SBusPLUS
stations
In the project example, the following devices are EtherCAT
®
/SBus
PLUS
stations:
The MOVI-C
®
CONTROLLER serves as EtherCAT
®
/SBus
PLUS
master.
The application inverters serve as EtherCAT
®
/SBus
PLUS
slaves.
The configuration of the devices is performed in the MOVISUITE
®
engineering soft-
ware.
The EtherCAT
®
/SBus
PLUS
stations are configured in several process steps:
1. "Establishing a connection between engineering PC and
MOVI‑C
®
CONTROLLER"(→236)
2. "Scanning the network for devices"(→238)
3. "Applying MOVI-C
®
devices to MOVISUITE
®
"(→239)
5.1.1 Establishing a connection between engineering PC and MOVI-C
®
CONTROLLER
To ensure that the engineering PC can communicate via the engineering interface
X80, X82 with the MOVI‑C
®
CONTROLLER via Ethernet, both the devices must be
connected in the same local network. For this purpose, the IP address parameters of
the engineering PC must be set to the local network.
INFORMATION
In delivery state, the engineering interface X80, X82 of the MOVI-C
®
CONTROLLER
has the following IP address parameters: Standard IP address 192.168.10.4, subnet
mask 255.255.255.0
Proceed as follows:
1. Select the network settings in the Windows control panel.
2. Double-click on the adapter that is physically connected to the engineering inter-
face X80, X82 of the MOVI‑C
®
CONTROLLER.