Doc# E145701 6 - 18
6: Using the Shark® 100 Meter
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Figure 6.5: Using the Watt-hour Test Pulse
Table 6.1: Infrared & KYZ Pulse Constants for Accuracy Testing - Kh Watt-hour per pulse
NOTES:
• Minimum pulse width is 40 milliseconds.
• Refer to Chapter 2, Section 2.2, for Wh Pulse specifications.
Input Voltage Level Class 10 Models Class 2 Models
Below 150V 0.2505759630 0.0501151926
Above 150V 1.0023038521 0.2004607704
-
-
-
A
B
C
MENU ENTER
MAX
MIN
LM1
LM2
%THD
PRG
VOLTS L-N
VOLTS L-L
AMPS
WNARP
VA/Hz
lrDA
Wh
VARh
VAh
120%-
90%-
60%-
30%-
%LOAD
MEGA
KILO
Wh Pulse
Comparator
Energy
Standard
Error
Results
Test Pulses Energy Pulses