Parameter Description
Parameter Description
114
• The diagram is as follows:
5.47 Zero-speed Function (P.151~P.152) V/F
P.151 “Zero-speed control function selection”
P.152 “Voltage instruction at zero-speed control”
The user must set the value of P.13 zero when using this
function.
Parameter
Factory Setting
Setting Range
Remarks
151 0 0~1
0 There are no output at zero speed
1 Control by DC (Note 1)
152 5% 0~30% (Note 2)
5.48 Over Torque Detection (P.155~P.156, P.260)
P.155 “Over torque detection level”
P.156 “Over torque detection time”
P.260“Over torque detection selection”
When the value of P.155 is not 0, the function of over torque detection is selected.
When the output current is in the excess of the over torque detection level P.155 and the over torque detection
time P.156, the screen of the inverter will display .
If the multi-function output terminal SO-SE (P.40) or the multi-function relay ABC (P.85) are set as over torque
Note: 1.The output mode selected by the value of P.151: when P.151 is 0, there is no output; when P.151 is 1, the
value of P152 is the voltage output dc voltage to keep the torque.
2. Suppose that P.152=6%, then the output voltage is P.19×6% at zero-speed.
3. This function is only effective in V/F mode.Motor control mode to set see parameters p. 300

Table of Contents

Other manuals for Shihlin electric SS2 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Shihlin electric SS2 Series and is the answer not in the manual?

Shihlin electric SS2 Series Specifications

General IconGeneral
BrandShihlin electric
ModelSS2 Series
CategoryInverter
LanguageEnglish

Related product manuals