5.65 Options for Stopping the Cooling Fan (P.245)
P.245 “Cooling fan operation selection”
Parameter Factory setting Setting range Remarks
245 1 0~3 ---
<Setting>
• When P.245=0, the fan will be turned on by the RUN signal. The fan will be turned off 30 seconds
after the inverter stops.
• When P.245=1, turning on the power will turn on the fan. When the power is turned off, the fan will
be off, too.
•When P.245=2, the fan will be turned on if the temperature of the heat sink is higher than 60℃ and
will be turned off if the temperature of the heat sink is lower than 40℃. When the inverter stops,
the fan will be off, too.
•When P.245=3, the fan will be turned on when the temperature of the heat sink is higher than 60℃.
and will be turned off when the temperature of the heat sink is lower than 40℃.