Parameter Description
Parameter Description
132
5.65 Options for Stopping the Cooling Fan (P.245)
P.245 “Cooling fan operation selection”
Parameter Factory setting Setting range Remarks
245 1 0~3 ---
<Setting>
• When P.245=0, the fan will be turned on by the RUN signal. The fan will be turned off 30 seconds
after the inverter stops.
• When P.245=1, turning on the power will turn on the fan. When the power is turned off, the fan will
be off, too.
•When P.245=2, the fan will be turned on if the temperature of the heat sink is higher than 60 and
will be turned off if the temperature of the heat sink is lower than 40. When the inverter stops,
the fan will be off, too.
•When P.245=3, the fan will be turned on when the temperature of the heat sink is higher than 60.
and will be turned off when the temperature of the heat sink is lower than 40.