Parameter Description
Parameter Description
57
Parameter Factory Setting Setting Range Remarks
22 200% 0~250% ---
23 9999 0~200%, 9999
When P.23=9999, stall prevention
operation level is the set value of P.22.
66
50Hz
0~650Hz
When P.189=1
60Hz When P.189=0
<Setting>
• During the period of starting a motor or increasing the output frequency, the output current of the
inverter will increase. Once the output current exceeds the pre-set upper limit (as in the following
figure), adjustment of the output frequency will be paused automatically and will not proceed until
the motor has reached the output frequency (at this moment, the output current of the inverter will
decrease correspondingly).
5.12 Output Frequency Filter Constant (P.28)
P.28 “Output frequency filter constant”
● Decreasing the acceleration/deceleration time or altering the output frequency from high-frequency
to low-frequency or vice versa can cause machine vibration and thereby affecting the product
quality.
● To reduce the machine vibration, the output frequency can be filtered when altering from
high-frequency to low-frequency or vice versa by setting the output frequency filter constant P.28.
The bigger the set value of P.28, the better the filter effect, but the corresponding response delay
will increase. The filter function is invalid if the set value of P.28 is 0.
Parameter Factory Setting Setting Range Remarks
28 0 0~31 ---