Parameter Description
Parameter Description
45
5.1 Torque Boost (P.0, P.46) V/F
P.0 “Torque boost”
P.46 “The second torque boost”
For an inverter controlled by the V/F mode, the starting torque is usually inadequate when starting
the motor because the output voltage of the inverter is inadequate. In this case, improve the output
voltage by setting up a proper torque boost (P.0) to obtain a better starting torque.
Parameter Factory Setting Setting Range Remarks
0
6%(0.4Kw~0.75Kw)
0~30% --- 4%(1.5Kw~3.7Kw)
3%(5.5Kw)
46 9999 0~30%, 9999 9999: function invalid
<Setting>
• If P.0=6% and P.19=220V, and output frequency of the inverter is 0.2Hz, the output voltage will be:
• If RT is ‘ON’, P.46 The Second Torque Boost will be valid.
Note: 1. A too large set value of P.0 may cause actions of the current protection of the inverter or the inverter will be
disabled for a smooth start.
2. The second function is valid only when P.44 is not equal to 9999.
3. RT in this paragraph is referred to as the multi-function control terminals. For selecting the function and
using the multi-function control terminal, please refer to P.80~P.84, P.86. For the wiring, please refer to
Section 3.5.6.

Table of Contents

Other manuals for Shihlin electric SS2 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Shihlin electric SS2 Series and is the answer not in the manual?

Shihlin electric SS2 Series Specifications

General IconGeneral
BrandShihlin electric
ModelSS2 Series
CategoryInverter
LanguageEnglish

Related product manuals