Parameter Description
Parameter Description
115
alarm (set the value to 12), the inverter will send out OL2 signal; If the multi-function output terminal SO-SE
(P.40) or the multi-function relay ABC (P.85) are set as over load alarm (set the value to 3), only when P.260=1,
will inverter send out OL signal. Please refer to P.40, P.85 for the details.
Parameter
Factory Setting
Setting Range
Remarks
155 0% 0~200%
0 No detection for over torque
0.1~200%
Detection for over torque
156 1s 0~60s ---
260 1 0, 1
0
The OL2 alarm is not reported after the
over torque detection, and the inverters
continue to running.
1
The OL2 alarm is reported after the
over torque detection, and the inverters
stop.
5.49 External Terminals Filter Adjusting Function (P.157)
P.157 “External terminals filter adjusting function”
Parameter Factory Setting Setting Range
157 4 ms 0~200ms
• P.157 selects response time to the signal of external terminal.

Table of Contents

Other manuals for Shihlin electric SS2 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Shihlin electric SS2 Series and is the answer not in the manual?

Shihlin electric SS2 Series Specifications

General IconGeneral
BrandShihlin electric
ModelSS2 Series
CategoryInverter
LanguageEnglish

Related product manuals