Parameter Description
Parameter Description
93
<Setting>
When the motor is running, the output voltage will not be constant once the driving power is
interrupted. When the power is recovered, the inverter will not restart automatically if P.57=9999. If
P.57=0.1~5, the motor will coast for a while (the set value of P.57), and then the inverter will restart
the motor automatically.
Once the motor is automatically restarted, the output frequency of the inverter will be the target
frequency, but the output voltage will be zero. Then the voltage will be increased gradually to the
expected voltage value. The period for the voltage increase is called the Restart cushion time (P.58).
• P.150 has four digits, and each digit has a distinct meaning. Their positions are as following:
Note: 1. P.150 must be set when using the restart function,
2. When the value of P.150 is not 0, default linear acceleration/deceleration curve.
3. If the single digit of P.150 is 1, P.150 cannot write-in.

Table of Contents

Other manuals for Shihlin electric SS2 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Shihlin electric SS2 Series and is the answer not in the manual?

Shihlin electric SS2 Series Specifications

General IconGeneral
BrandShihlin electric
ModelSS2 Series
CategoryInverter
LanguageEnglish

Related product manuals