8 Commissioning
8.1 Overview
Prerequisites
•
Pr
oject planning is completed.
•
Mounting is completed.
•
Electrical installation is completed.
•
Dangerous state of the machine is and remains off during commissioning.
•
The outputs of the device do not affect the machine during commissioning.
•
The machine has been inspected and released by qualified safety personnel.
•
Protective device works properly.
•
The protection function is checked after each change to the machine or to the
integration or the operating and boundary conditions of the device.
Approach
1.
Check the DIP switches at the sender and receiver and set them correctly if
required.
2. Fitting the system plug.
3. Switch on the voltage supply.
°
If a change to the configuration is detected or the device has been reset to
factory settings, the device is in configuration mode and the field indicator
flashes green.
4. Configure the restart interlock if required.
5. Once configuration is complete, briefly interrupt the voltage supply, then switch it
back on.
6. If the configuration for the restart interlock or external device monitoring needs to
be changed, reset the device to factory settings.
7. Once configuration is complete and the device has been restarted, align the
sender and receiver.
8. Briefly interrupt the voltage supply, then switch it back on.
9. Check alignment.
10. Check the contactors.
Further topics
•
"Pr
oject planning", page 21
•
"Mounting", page 41
•
"Electrical installation", page 51
•
"Configuration", page 55
•
"Mounting the system plug", page 41
•
"Configuration mode", page 57
•
"Configuring the restart interlock", page 58
•
"Factory settings", page 55
•
"Sender and receiver alignment", page 62
•
"Check during commissioning and modifications", page 66
8.2 Switching on
Overview
Af
ter switching on, the sender and receiver initialize. All LEDs on the sender and
receiver will light up briefly. They then indicate the following information:
•
If a change to the configuration is detected or the device has been reset to factory
settings, the device is in configuration mode and the field indicator flashes green
•
The field indicator and diagnostic LEDs indicate the current configuration
COMMISSIONING 8
8028570/2023-07-27 | SICK O P E R A T I N G I N S T R U C T I O N S | deTec4 C4P-EAxxx3SC05
61