8011952/YWL2/3-0/2016-08| SICK OPERATING INSTRUCTIONS | DUSTHUNTER C200
Subject to change without notice
ASSEMBLY AND INSTALLATION 3
3.3.4 Connecting the MCU control unit
Fig. 26: Component layout in the MCU (without purge air supply, with options)
3.3.4.1 Work to be done
Connect the connection line: see “Standard connection”, page 50.
Connect lines for status signals (operation/failure, maintenance, function check, mainte-
nance request, limit value), analog output, analog and digital inputs according to require-
ments (see “Standard connection”, page 50, p. 53, Fig. 31 and Fig. “Terminal
assignment of analog input module”; only use shielded lines with twisted pairs).
Connect power line to terminals L1, N, PE of the MCU (see “Component layout in the
MCU (without purge air supply, with options)”, page 47).
Close off unused line openings with dummy plugs.
DISPLAYMODUL
relay 3 relay 4 relay 5
BUS
Ter m
Ter m
relay 1 relay 2
com nc. no.com nc. no. com nc. no.com nc. no. com nc. no.
Reset
Optional Interface module
Processor board
Optional Display module
Optional I/O modules
Terminals for power connection
If an onsite line is to be used, it must be connected to a suitable 7-pole socket (see
“Plug connector connection to onsite line”, page 49; SICK Part No.: 7045569).
NOTICE:
Only use shielded lines with twisted pairs (e.g., UNITRONIC LiYCY (TP) 2 x
2 x 0.5 mm² from LAPPKabel; 1 pair of wires for RS 485, 1 pair of wires
for power supply; not suitable for underground laying).
WARNING:
Be sure to check the wiring before switching the supply voltage on.
Only modify wiring when disconnected from the power supply and potential-
free.