DL100 – CANopen
®
Distance measuring device
OPERATING INSTRUCTIONS

Table of Contents

Questions and Answers

  • M
    Mary ChoiSep 23, 2025
    Why does the display show "0000" on my SICK Measuring Instruments?
    • B
      benjamin14Sep 23, 2025
      If the display on your SICK Measuring Instruments shows "0000", it could be due to a few reasons: * The measuring device's light spot is not hitting the reflector. Ensure correct alignment between the measuring device and reflector. * There is an obstacle in the light path. Remove any obstructions. * The distance between the measuring device and the reflector exceeds the maximum scanning range. Decrease the distance or select a device with a larger scanning range.
  • S
    shelby42Aug 23, 2025
    What to do if SICK Measuring Instruments show 'wPlb' error?
    • R
      Robert PooleAug 25, 2025
      If the measured value from your SICK Measuring Instruments is not plausible (wPlb), it's likely because the light path between the measuring device and the reflector is interrupted. Observe the light spot on the reflector to ensure it remains steady. If needed, realign the measuring device and reflector, or consider using a larger reflector. Also, it may be caused by optical interferences. Remove any optical interferences and realign the measuring device and reflector.
  • R
    Ronald MunozAug 25, 2025
    What does 'wLevel' mean on SICK Measuring Instruments and how to fix it?
    • A
      Albert AdkinsAug 26, 2025
      The error message 'wLevel' on your SICK Measuring Instruments indicates that the current damping value is below the recommended level. To resolve this: * Clean any external lens surfaces like the reflector and the lens. * Decrease the distance between the measuring device and the reflector. * Use a distance measuring device with a higher range.
  • S
    Sandra MillsAug 27, 2025
    What does 'wTemp' indicate on SICK Measuring Instruments and how can I resolve it?
    • K
      Kathryn TurnerAug 27, 2025
      The error message 'wTemp' on your SICK Measuring Instruments indicates that the internal device temperature is nearing the permissible range. Here are some possible solutions: * Check the ambient temperature and improve ventilation if needed. * Shield the device against radiation heat, such as direct sunlight. * Use a device with heating at low ambient temperatures. * Use cooling housings for high ambient temperatures.
  • J
    Jessica HernandezAug 27, 2025
    What does 'wLaser' mean on SICK DL100?
    • D
      Dana ClarkAug 27, 2025
      The error message 'wLaser' on your SICK Measuring Instruments means that the measurement laser is still working but is nearing the end of its service life. Keep a replacement device ready.
  • T
    Tara GilbertSep 16, 2025
    What to do if eLaser error appears on SICK DL100?
    • L
      Lindsay JonesSep 16, 2025
      If the service life of a measurement laser is exceeded (eLaser) on your SICK Measuring Instruments device, you should replace the measuring device.
  • B
    Bonnie DiazSep 13, 2025
    What causes measuring errors in SICK DL100 Measuring Instruments?
    • S
      Steven BakerSep 13, 2025
      If you encounter a measuring error with the SICK Measuring Instruments, it might be because the light path between the measuring device and reflector is interrupted, the current damping value is below the recommended value, the lens or reflector is contaminated or the movement is too fast. To solve this: * Keep a replacement device ready. * Clean external lens surfaces like the reflector and the lens. * Check the maximum movement speed.
  • V
    Victor BowersSep 15, 2025
    What causes pre-failure recognition in SICK Measuring Instruments?
    • M
      Mary MartinSep 15, 2025
      If you're experiencing pre-failure recognition with the SICK Measuring Instruments, it could be due to several reasons: * The measurement laser is nearing the end of its service life. Keep a replacement device ready. * The current damping value is below the recommended value. Clean external lens surfaces like the reflector and the lens. * The lens or reflector is contaminated. Clean external lens surfaces like the reflector and the lens. * The internal device temperature is within the threshold range. Check the ambient temperature.
  • A
    Ashley PalmerSep 5, 2025
    What to do if wPlb error appears on SICK Measuring Instruments?
    • I
      Isaiah HodgesSep 5, 2025
      If the measured value is not plausible (wPlb) on your SICK Measuring Instruments, it may be because the light path between the measuring device and reflector is interrupted or due to optical interferences. To resolve this: * Observe the light spot on the reflector to ensure it doesn't move from the reflector. Re-align the measuring device and reflector if needed, or use a larger reflector. * Remove any optical interferences, and re-align the distance measuring device and reflector.
  • J
    johnsonmarkSep 3, 2025
    What to do if 'Device error' appears on SICK Measuring Instruments?
    • K
      Karen JimenezSep 3, 2025
      If you see the 'Device error' on your SICK Measuring Instruments, it could be due to hardware issues or the internal device temperature being outside the permissible range. Here's what you can do: * Check the supply voltage and wiring. * Switch the supply voltage on and off. * Wait for the warm-up phase or let the device cool down. * Check the ambient temperature and improve ventilation if needed. * Shield against radiation heat by shading the device from direct sunlight. * Consider using a device with heating for low ambient temperatures or cooling housings for high temperatures. * If the problem persists, send the measuring device in for repair.

Summary

Operating Instructions DL100 - CANopen

Important Safety Notes

Critical safety information for device operation, including laser safety.

General Information

Basic details about the manual, symbols, liability, delivery, and service.

Safety Guidelines

Comprehensive safety rules, intended/non-intended use, and personnel requirements.

Device Identification

Information for identifying the device, including the type label.

Setup and Functionality

Guidance on physical setup, operational principles, display, and controls.

Transport and Storage

Procedures for safe transport, inspection, and storage of the device.

Mounting Instructions

Detailed steps and considerations for installing the distance measuring device.

Electrical Connection

Safety precautions and diagrams for connecting the device electrically.

Operation of the Measuring Device

Instructions for device operation, parameter selection, and value changes.

Operation via Ethernet Interface

Configuration and operation using the Ethernet interface and SOPAS ET.

CANopen Interface

Comprehensive guide to CANopen communication, configuration, and objects.

Cleaning and Maintenance

Procedures for cleaning and routine maintenance of the device.

Troubleshooting Guide

Diagnosing and resolving common issues using LED status, warnings, and errors.

Repair and Technical Data

Information on repair policies and detailed technical specifications.

Device Accessories

Details on available accessories like reflectors, cables, and mounting systems.

Menu Structure

Visual representation of the device's navigation hierarchy and parameters.

SICK DL100 Specifications

General IconGeneral
Wave length650 nm
Resolution0.1 mm
Output signalAnalog
Supply voltage10 V DC ... 30 V DC
Beam Diameter3 mm
Operating Temperature-10 °C ... +50 °C
Storage Temperature-25°C to +70°C
Power SupplyDC