ou select the 30 mm resolution, the protective field that can be configured is
smaller (for smaller hazardous points to be protected), however you can mount the
safety laser scanner closer to the hazardous point.
If you select the 40 mm resolution, the protective field that can be configured is
larger (i.e., for larger hazardous points to be protected). In this case, however, you
have to mount the safety laser scanner further away from the hazardous point.
1
Figure 36: Minimum distance to hazardous area
1
Contour of the floor and side panels as a reference
PROJECT PLANNING 4
8012029/ZA20/2019-11-14 | SICK O P E R A T I N G I N S T R U C T I O N S | S3000 Cold Store
45
Subject to change without notice