NOTE
T
his function can only be used in conjunction with a Flexi Soft safety controller that is
connected via EFI.
Triple
If y
ou select the Triple option, you can configure field sets with three fields. These field
sets comprise one protective field and two warning fields.
Further topics
•
"Simultaneous monitoring", page 88
7.6.5 Exchange of field results via EFI
DANGER
Incorrect signal evaluation
The dangerous state may not be stopped in the event of non-compliance.
b
Note the logical values of the status information of the protective fields when
transferred to the Flexi Soft safety controller.
•
T
he status of an evaluated protective field is logical 1 if the protective field is clear.
•
The status is logical 0 if the protective field is interrupted.
•
The status of an unallocated protective field defaults initially to logical 1.
If you evaluate the status of the protective fields using Flexi Soft, then on the Resolution/
field mode tab first select the Transfer unallocated fields as interrupted option.
If you have selected the Dual protective fields field mode, then the Transfer unallocated fields
as interrupted option is selected automatically.
Further topics
•
"E
FI status information and control commands", page 116
7.7 Inputs
Overview
It is pos
sible to switch between the monitoring cases of the safety laser scanner during
operation. The following options are available for doing this:
CONFIGURATION 7
8012029/ZA20/2019-11-14 | SICK O P E R A T I N G I N S T R U C T I O N S | S3000 Cold Store