TÜV SÜD Product Service is an NRTL approved by OSHA and undertakes product
certifications for industrial controls, electric drives and other products. The following
links lists the approved NRTL laboratories:
https://www.osha.gov/dts/otpca/nrtl/nrtllist.html
The tested devices are labeled with the following symbol:
The device series 0362X49xy/0362129xy is tested accoring to the harmonized
standard IEC / UL 61800-5-1: “Standard for Adjustable Speed Electrical Power Drive
Systems – Part 5-1: Safety Requirements – Electrical, Thermal and Energy”
Date: 2016-11-17, extended on 2018-04-25
Power converter:
0362149EF / 0362249EF / 0362129EF
0362149IF / 0362249IF / 0362129IF
0362149EC / 0362249EC / 0362129EC
0362149IC / 0362249IC / 0362129IC
Certificate number: U8V 16 11 96098 005
Certificate data base:
https://www.tuev-sued.de/product-testing/certificates
(Enter “SIEB & MEYER AG” in the search field.)
http://www.tuev-sued.de/industry-and-consumer-products/-services/nationally-
recognized-testing-laboratory-nrtl
http://www.tuev-sued.de/industry-and-consumer-products/-branches/industrial-
electronics
2.2 NRTL Requirements
Points of Exceptions of the Test Procedure and Conditions of Acceptability
Conditions of Acceptability:
When installing, requirements of mentioned Test Standards and Installation Guide
have to be fulfilled.
The equipments are intended for use in end-use application within final enclosure
to maintain a pollution degree 2 or equivalent environment.
The final enclosure has to fulfill the requirements for the protection in case of
direct contact.
Maximum Surrounding Air Temperature: +40 °C.
The Terminal blocks are suitable for factory wiring only.
The end-use application must be equipped with a Branch Circuit Protection that
meets the requirements of the NRTL certificate.
All Branch Circuit Protection shall have characteristic B.
The diameter of the protective earthing conductor shall be 10 mm² (AWG 8) or
higher.
General Information
W
14 Drive System SD2S - Hardware Description 0362X49xy / 0362129xy
2

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the SIEB & MEYER SD2S 0362X49xy and is the answer not in the manual?

SIEB & MEYER SD2S 0362X49xy Specifications

General IconGeneral
BrandSIEB & MEYER
ModelSD2S 0362X49xy
CategoryDC Drives
LanguageEnglish

Related product manuals