Representation of the analog values of analog modules
5.1 Representation of the analog values of analog input channels
S7-300 Automation System Module data
Manual, 08/2006, A5E00105505-04
5-15
Representation of the analog values of thermocouples type L
Table 5-27 Representation of the analog values of thermocouples type L
Units Units Units
Type L in
°C
dec hexa-
decimal
Type L in °F
dec hexa-
decimal
Type L in K
dec hexa-
decimal
Range
> 1150.0 32767 7FFF
H
> 2102.0 32767 7FFF
H
> 1423.2 32767 7FFF
H
Overflow
1150.0
:
901.0
11500
:
9010
2CEC
H
:
2332
H
2102.0
:
1653.8
21020
:
16538
521C
H
:
409A
H
1423.2
:
1174.2
14232
:
11742
3798
H
:
2DDE
H
Overshoot
range
900.0
:
-200.0
9000
:
-2000
2328
H
:
F830
H
1652.0
:
-328.0
16520
:
-3280
4088
H
:
F330
H
1173.2
:
73.2
11732
:
732
2DD4
H
:
02DC
H
Nominal
range
< -200.0 < -2000 < F830
H
< -328.0 < -3280 < F330
H
< 73.2 < 732 <02DC
H
Underflow
Faulty wiring (polarity reversal, or open inputs, for example), or transducer error in the negative range
(wrong type of thermocouple, for example) will cause the analog input module to signal underflow, starting
at ...
... F380
H
, and to output 8000
H
. ... EAC0
H
, and to output 8000
H
. ... FE2C
H
, and to output 8000
H
.
Representation of the analog values of thermocouples type N
Table 5-28 Representation of the analog values of thermocouples type N
Units Units Units
Type N in
°C
dec hexa-
decimal
Type N in
°F
dec hexa-
decimal
Type N in K
dec hexa-
decimal
Range
> 1550.0 32767 7FFF
H
> 2822.0 32767 7FFF
H
> 1823.2 32767 7FFF
H
Overflow
1550.0
:
1300.1
15500
:
13001
3C8C
H
:
32C9
H
2822.0
:
2373.8
28220
:
23738
6E3C
H
:
5CBA
H
1823.2
:
1574.2
18232
:
15742
4738
H
:
3D7E
H
Overshoot
range
1300.0
:
-270.0
13000
:
-2700
32C8
H
:
F574
H
2372.0
:
-454.0
23720
:
-4540
5CA8
H
:
EE44
H
1573.2
:
0
15732
:
0
3D74
H
:
0000
H
Nominal
range
< -270.0 < -2700 < F574
H
< -454.0 < -4540 <EE44
H
< 0 < 0 < 0000
H
Underflow
Faulty wiring (polarity reversal, or open inputs, for example), or transducer error in the negative range
(wrong type of thermocouple, for example) will cause the analog input module to signal underflow, starting
at ...
... F0C4
H
, and to output 8000
H
. ... E5D4
H
, and to output 8000
H
. ... FB70
H
, and to output 8000
H
.

Table of Contents

Other manuals for Siemens 6ES7 305-1BA80-0AA0

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens 6ES7 305-1BA80-0AA0 and is the answer not in the manual?

Siemens 6ES7 305-1BA80-0AA0 Specifications

General IconGeneral
BrandSiemens
Model6ES7 305-1BA80-0AA0
CategoryController
LanguageEnglish

Related product manuals