Analog modules
6.8 Analog input module SM 331; AI 2 x 12 bit; (6ES7331-7KB02-0AB0)
S7-300 Automation System Module data
6-72 Manual, 08/2006, A5E00105505-04
6.8.3 Additional information to SM 331; AI 2 x 12 bit
Unused channels
You must short-circuit unused channels and connect them to M
ANA
. This optimizes
interference immunity of the analog input module. For unused channels, set the "disabled"
instruction at the "measuring method" parameter. This reduces the module's cycle time.
If not used, short-circuit the COMP input.
Certain inputs of the channel group configuration may remain unused. To enable diagnostic
functions at the used channels, note the special features of those inputs outlined below:
Measuring range 1 V to 5 V: wire the used and unused inputs of the same channel group
in parallel.
Current measurement, 2-wire transmitter: There are two ways to wire the channel circuit:
a) Open unused input; channel group diagnostics disabled. If you were to enable
diagnostics, the analog module would trigger a single diagnostic interrupt, and light up its
SF LED.
b) Terminating the unused input using a 1.5 kΩ to 3.3 kΩ resistor. This allows you to
enable diagnostics for this channel group.
Current measurement 4 mA to 20 mA, 4-wire transducer: wire the unused inputs of the
same channel group in series.
Wirebreak monitoring
The wire-break check function is designed only for temperature measurements
(thermocouples and thermoresistors.)
Special features of the wire-break check function in the 4 mA to 20 mA measuring range
If you configured a measuring range of 4 mA to 20 mA, and enabled wire-break check, the
analog input module logs a wire-break event in diagnostics data when the current drops
below 3.6 mA.
The module also triggers a diagnostic interrupt if you enabled diagnostics interrupts in the
program.
The lit SF LED is otherwise the only indication of the wire-break, and you must evaluate the
diagnostic bytes in the user program.
If you configured a measuring range of 4 mA to 20 mA, disabled wire-break check, and
enabled diagnostic interrupts, the module triggers a diagnostic interrupt when the underflow
value is reached.

Table of Contents

Other manuals for Siemens 6ES7 305-1BA80-0AA0

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens 6ES7 305-1BA80-0AA0 and is the answer not in the manual?

Siemens 6ES7 305-1BA80-0AA0 Specifications

General IconGeneral
BrandSiemens
Model6ES7 305-1BA80-0AA0
CategoryController
LanguageEnglish

Related product manuals