1.12 Rapid roaming
Wireless Teach Pendant F IWLAN V2
Operating Instructions, 08/2010, A5E02453837-01
31
For stable PNIO communication, a WLAN client should be located at all times in a radio cell
with a signal strength > 60% or > -65 dBm. This can be checked by switching the various
segments on and off.
This does not mean that the client needs to change over at a signal strength < 60% or < -65
dBm. Make sure that a segment is available with a sufficiently powerful signal.
Limitations due to iPCF-MC
iPCF-MC is an in-house development of the Siemens AG that will only work with participants
in which iPCF-MC has been installed.
Operating principle of iPCF-MC
iPCF-MC uses both radio interfaces of the access point differently: One interface works as
management interface and sends a beacon every five milliseconds. The other interface
transmits the user data.
The following requirements have to be met to use iPCF-MC:
All "RR" versions of the SCALANCE W-700 access points with at least two WLAN
interfaces can be used as access point. The HMI device and all SCALANCE W-700 "RR"
versions are suited as clients.
You have to operate the management interface and the data interface in the same
frequency band; they also have to match in their radio coverage. iPCF-MC will not work if
both radio interfaces are equipped with directional antenna the cover different areas.
The management inferfaces of all access points that a client is to access must use the
same channel. A client will only scan this one channel to find all available access points.
You cannot use the transmission method to IEEE 802.11h for the management interface.
802.11h is possible for the data interface.