Overview
1.13 Terms for fail-safe operation
Wireless Teach Pendant F IWLAN V2
32 Operating Instructions, 08/2010, A5E02453837-01
1.13 Terms for fail-safe operation
Fail-safe automation system
A fail-safe automation system is required in a plant with high safety requirements.
In an EMERGENCY STOP, the fail-safe automation system brings the plant to a safe
operating state regardless of the situation. Shutdown of the plant therefore does not pose a
danger to people or the plant.
Fail-safe operation
The HMI device registers signals from the EMERGENCY STOP button and the enabling
button during fail-safe operation. The controller and the HMI device communicate via
PROFIsafe.
Configuration of the safety functions in STEP 7 with the "SIMATIC S7 Distributed Safety"
add-on package can achieve fail-safe operation according to SIL 3 or Performance Level e
and Category 4 for the HMI device.
Integration and removal
Integrating
Integration means to establish safety-related communication between the HMI device and
the fail-safe controller via PROFIsafe.
The EMERGENCY STOP button is enabled in integrated operating mode.
Removing
Removal means to intentionally stop safety-related communication between the HMI
device and the fail-safe controller via PROFIsafe.
Logging on the HMI device
The HMI device must be logged onto a machine in order to operate the machine after
integration in fail-safe operation with the enabling button. The logon is performed with an
RFID tag.
Logging off an HMI device
Logging off an HMI device from a machine terminates fail-safe operation with the enabling
button.
Forced logoff
If the security system is triggered, for example by the operator leaving the protection zone
without logging off, a forced logoff is performed by the machine. The HMI device revokes
the operator authorization for the enabling button. The operator is prompted to confirm
the "Forced logoff" dialog.
Automatic logoff in the event of a communication error