1.13 Terms for fail-safe operation
Wireless Teach Pendant F IWLAN V2
Operating Instructions, 08/2010, A5E02453837-01
33
If a communication error occurs, the HMI device is removed from the safety-related
communication. The HMI device is automatically logged off the machine. The fail-safe
controller brings the plant to a safe operating state.
Shutdown response of the plant
The following shutdown response of the plant applies regardless of whether or not the
HMI device is logged onto a machine.
EMERGENCY STOP
EMERGENCY STOP is a procedure that is intended to stop a process or movement
associated with danger in accordance to EN 60204-1, Appendix D. An EMERGENCY
STOP immediately stops all parts of the plant controlled by the fail-safe controller via a
safety program. The EMERGENCY STOP button is always enabled when there is
PROFIsafe communication between HMI device and fail-safe controller, i.e. when the
HMI device is integrated in the PROFIsafe communication.
Global rampdown
A global rampdown is the intentional stopping of the plant. The global rampdown is
independent of the area.
The global rampdown is triggered by the fail-safe controller, for example, if an error
occurs with an HMI device integrated in the PROFIsafe communication.
The following shutdown response of the plant applies when the HMI device is logged onto
a machine.
Local rampdown
A local rampdown is the intentional stopping of a plant section by the fail-safe
controller. The local rampdown is triggered, for example, when the operator leaves the
protection zone without logging off via a security system.
Shutdown
The shutdown is triggered when the F-CPU has detected a communication error with
an HMI device that is logged onto a machine. Shutdown is the immediate stop of all
machinery being operated in fail-safe mode.
Communication error
A communication error occurs when the communication between HMI device and fail-safe
controller is interrupted. Additional information is available in the section "Communication
error for the integrated HMI device (Pag
e 256)".