Programming Manual of FC2005/FC901
46|63 A6V10333724_b_en_--
Isolator Support When set as True, the device should be wired according to the
rules for isolator supported. Otherwise, the panel reports
trouble. When set as False (default), the device should be wired
as polar non-sensitive. Otherwise, the panel reports trouble as
well.
Multi Critieria Usage
(OOT/OOTC Channel)
Option 1: ASD (default)
Option 2: Photoelectric (alarm)
Option 3: Off
Multi Criteria Setting
(OOT/OOTC Channel)
Set the device application scenario. Users can select one
scenario from the drop-down list.
Only available when “Multi Critieria Usage” is set as “ASD”.
Photoelectric Setting
(OOT/OOTC Channel)
Only available when “Multi Critieria Usage” is set to
“Photoelectric(alarm)”.
Select one option from the drop-down list.
Thermal Alarm Usage
(OOT/OOTC Channel)
Option 1: Thermal Evaluation(default)
Option 2: Off
Thermal Alarm Setting
(OOT/OOTC Channel)
Select an option from the drop down list.
ROR: rate of rise
Silenceable
(output channel)
Bool: True (default) / False
Silenceable On
Waterflow
(output channel)
Available when “Silenceable” (output channel) is set as True.
Bool: True (default) / False
HoldThroughReset
(output channel)
Device won’t be reset when press Reset button on the panel.
Bool: True / False (default)
Volume
(Pri1/2. AudibleControl)
Maximum Volume (default)
Medium Volume
ToneType
(Pri1/2. AudibleControl)
Select one tone type from the drop-down list
Silenceable
(Pri1/2. AudibleControl)
Bool: True (default) / False
Silenceable On
Waterflow
(Pri1/2. AudibleControl)
Available when “Silenceable” (output channel) is set as True.
Bool: True (default) / False
HoldThroughReset
(Pri1/2. AudibleControl)
Device won’t be reset when press Reset button on the panel.
Bool: True / False (default)
FDOOT441
FDOOTC441
(Only available for
FC2005)
Name Name of the device
Name Addition Additional description of the device; max. 20 characters
Address Range: 1...50; System assigns one address automatically once
a device is added.
LED normal off Bool: True / False (default)
LED Activation Input Only (default)
Input or Output
Audible Base Type Unknown (default)
ABHW-4B
ABHW-4S

Other manuals for Siemens FC2005