Programming Manual of FC2005/FC901
A6V10333724_b_en_-- 47|63
Buzzer Base Powering Available when “ABHW-4B” is selected for “Audible Base Type”:
Detection Line Powered
NAC Powered
AUX/DC Powered (default)
Speaker Base
Powering
Available when “ABHW-4S” is selected for “Audible Base Type”:
NAC Powered
AUX/DC Powered (default)
Turn Off Bool: True/ False (default)
Isolator Support When set as True, the device should be wired according to the
rules for isolator supported. Otherwise, the panel reports
trouble. When set as False (default), the device should be wired
as polar non-sensitive. Otherwise, the panel reports trouble as
well.
Multi Critieria Usage
(OOT/OOTC Channel)
Option 1: ASD (default)
Option 2: Photoelectric (alarm)
Option 3: Off
Multi Criteria Setting
(OOT/OOTC Channel)
Set the device application scenario. Users can select one
scenario from the drop-down list.
Only available when “Multi Critieria Usage” is set as “ASD”.
Photoelectric Setting
(OOT/OOTC Channel)
Only available when “Multi Critieria Usage” is set to
“Photoelectric(alarm)”.
Select one option from the drop-down list.
Thermal Alarm Usage
(OOT/OOTC Channel)
Option 1: Thermal Evaluation(default)
Option 2: Off
Thermal Alarm Setting
(OOT/OOTC Channel)
Select an option from the drop down list.
ROR: rate of rise
Silenceable
(output channel)
Bool: True (default) / False
Silenceable On
Waterflow
(output channel)
Available when “Silenceable” (output channel) is set as True.
Bool: True (default) / False
HoldThroughReset
(output channel)
Device won’t be reset when press Reset button on the panel.
Bool: True / False (default)
Volume
(Pri1/2. AudibleControl)
Maximum Volume (default)
Medium Volume
ToneType
(Pri1/2. AudibleControl)
Select one tone type from the drop-down list
Silenceable
(Pri1/2. AudibleControl)
Bool: True (default) / False
Silenceable On
Waterflow
(Pri1/2. AudibleControl)
Available when “Silenceable” (output channel) is set as True.
Bool: True (default) / False
HoldThroughReset
(Pri1/2. AudibleControl)
Device won’t be reset when press Reset button on the panel.
Bool: True / False (default)
FDCIO422 Name Name of the device
Name Addition Additional description of the device; max. 20 characters