Operation
5
Switching off / Switching on
115
Building Technologies A6V10380629_en--_a
Fire Safety 2015-09-10
Switch off 'Section' temporarily
w You are logged onto at least 'Access level' 2.1.
w You are in 'Main menu'.
1. Select the 'Element search' menu item.
a The 'Element search' dialog window opens.
2. Open the filter 'Element category'.
a The 'Element category' filter opens.
3. Select 'Section'.
a The element category 'Section' is displayed in the filter 'Element category'.
4. Open the filter 'Element address'.
a The 'Element address' dialog window opens.
5. Enter the 'Element address' via the number pad and press 'Enter'.
a The 'Element address' of the 'Section' is displayed in the 'Element address'
filter.
6. Press 'Set'.
a The element search starts.
a The 'Section' is displayed and highlighted in the result list.
7. Press 'Execute commands' on the dialog window toolbar.
a The 'Select command' dialog window opens.
8. Select the 'All zones OFF/timer' menu item.
a The 'Set duration' dialog window is displayed.