Operation
5
Switching off / Switching on
109
Building Technologies A6V10380629_en--_a
Fire Safety 2015-09-10
5.3 Switching off / Switching on
To avoid false alarms or fault messages, you can switch off parts of a 'Site'
in certain situations, e.g., for the purpose of maintenance work.
When a part of a system is switched off, the 'Isolation' LED is on.
The situations in which part of a 'Site' should be switched off, depends on the
detectors used as well as on possible deceptive phenomena such as smoke, dust,
heat or vapour.
WARNING
System parts that have been switched off make it impossible to acquire and
process alarms or faults!
Fire may spread unhindered.
Deploy staff to monitor the deactivated area.
You must switch deactivated parts of the
'
Site
' back on as soon as possible.
If a deactivated '
Zone
' is the only '
Zone
' in a
'
Section
', the '
Section
' is also
indicated as deactivated.
Examples of switching off/on are provided in the following chapters.
5.3.1 Switching a detector zone off / on
The terms detector zone and 'Zone' are identical in terms of content.
WARNING
System part
s that have been switched off make it impossible to acquire and
process alarms or faults!
Fire may spread unhindered.
Deploy staff to monitor the deactivated area.
You must switch deactivated parts of the
'
Site
' back on as soon as possible.
If a deactivated '
Zone
' is the only '
Zone
' in a
'
Section
', the '
Section
' is also
indicated as deactivated.
Yo
u will find information on temporarily isolating detector zones in chapter
'Temporary switching-off [ 114]'.
In which situations a detector zone should be switched off, depends on the
detectors used as well as on possible deceptive phenomena such as smoke, dust,
heat or vapour.
The fastest method for switching off or on is to enter a known address in the
'Element address' dialog window.
In the configuration, a standard button can be given the function of directly
opening the menu with the 'Element address' dialog window to select a detector
zone.
In the following exemplary operating sequence the process is shown without a
known address.

Table of Contents

Other manuals for Siemens FT2080

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens FT2080 and is the answer not in the manual?

Siemens FT2080 Specifications

General IconGeneral
BrandSiemens
ModelFT2080
CategoryTouch terminals
LanguageEnglish

Related product manuals