5
Operation
Testing
136
Building Technologies A6V10380629_en--_a
Fire Safety 2015-09-10
Ending 'Detector test' for all automatic 'Detectors' in an 'Area'
1. Repeat steps 1 - 7 of the instruction: Test all automatic 'Detectors' of a 'Area.
a The 'Select command' dialog window opens.
2. Select the 'Non-MCP zones det.test END' command.
a The 'DETECTOR TEST' LED goes out.
a The command execution display confirms successful execution of the
command by displaying .
a The 'Detector test' is at an end.
5.7.2 Carrying out the walk test
l Proceed as with 'Detector test' and select the 'Walk test' function.
5.7.3 Carrying out an installation test
As in the 'Installation test' all functions of the complete fire detection system
including the 'Fire control' and alarming are tested, you must take appropriate
actions.
The 'Installation test' can be carried out at 'Area' or 'Section' levels.
WARNING
During the installation test, the alarming and
fire control are activated!
Personal injury resulting from extinguishing activation
The fire brigade is called up unnecessarily.
Set the 'Fire controls' to 'Control test' in advance.
Inform the fire brigade in advance.
Before the '
Installation test
' you can set '
Fire controls
' to '
Control test
'.
No activation of manual call
point zones
Manual call point zones are not activated in the 'Installation test'. The 'Installation
test' is not available for manual call point zones.

Table of Contents

Other manuals for Siemens FT2080

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens FT2080 and is the answer not in the manual?

Siemens FT2080 Specifications

General IconGeneral
BrandSiemens
ModelFT2080
CategoryTouch terminals
LanguageEnglish

Related product manuals