5
Operation
Switching off / Switching on
114
Building Technologies A6V10380629_en--_a
Fire Safety 2015-09-10
a The 'Select command' dialog window opens.
8. Select the 'OFF' command.
a The command is executed.
a The command execution display confirms successful execution of the
command by displaying .
a The 'Detector' is switched off.
Switching on the 'Detector'
Proceed as before with 'Detector' and select the command 'ON'.
As an alternative, you can also select the corresponding detector or '
'Message summary' main menu item and the 'Isolations' message category and
switch it back on with the 'MoreOptions', 'Execute commands', and 'ON' softkey.
5.3.3 Temporary switching-off
The 'Temporary switching-off' function can be used to set a time limit for 'Isolation'.
The switched off part of the 'Site' is switched back on automatically after the time
period entered.
WARNING
System parts that have been switched off make it impossible to acquire and
process alarms or faults!
Fire may spread unhindered.
● Deploy staff to monitor the deactivated area.
You must switch deactivated parts of the ↑
' back on as soon as possible.
'Detector'.
Override for different settings
If a detector has been temporarily isolated and its '
isolated, the detector is also permanently isolated.
f a detector has been temporarily isolated and its '
isolated, the time limit for the isolation of the 'Zone' also applies for the detector.
' have been isolated and the time limit for the isolat
a detector elapses, the 'Zone' is displayed as switched on.