5
Operation
Settings / Administra
tion
152
Building Technologies A6V10380629_en--_a
Fire Safety 2015-09-10
4. Select a setting.
a The command execution display confirms successful execution of the
command by displaying .
a The touch screen brightness has been set.
5.9.5 Setting the buzzer volume
You can set the sound level of the 'Station' buzzer on four levels or switch it off.
NOTICE
Buzzer volume too low
Non-compliance with EN 54-2 Para 12.10.2
Set the buzzer sound level to the maximum.
As per EN 54-2, the minimum sound level at a distance of 1 m must reach the
following values, measured under open air conditions:
-60 dB (A) for announcing fire alarm signals
-50 dB (A) for announcing fault messages
'Set buzzer volume'
w You are logged onto 'Access level' 2.2.
w You are in 'Main menu'.
1. Select the 'Settings/administration' menu item.
a The 'Settings/administration' menu is displayed.