Operation
5
Switching off
/ Switching on
117
Building Technologies A6V10380629_en--_a
Fire Safety 2015-09-10
5.3.4 Switching off / on the remote transmission Fire
WARNING
When the remote transmission Fire has been switched off, the fire brigade cannot
be called up in the event of fire!
Fire may spread unhindered.
Deploy staff to monitor the 'Site'.
You must switch the '
RT Fire
' back
on as soon as possible.
The '
RT Fire
' is normally switched on and may only be switched off in particular
cases, e.g. for a function check of controls.
Remote transmission, fire can be switched off in the following two ways. Both ways
are then shown.
l Switch off 'RT Fire' via the 'Topology' dialog window.
l Switch off 'RT Fire' via the 'Functions' menu item.
Switch off 'RT Fire' via the 'Topology' dialog window
w You are logged onto at least 'Access level' 2.1.
1. Press the button 'Topology' on the GTB.
a The 'Topology' dialog window opens.
2. Press 'Lower level' in the 'Control tree' list entry.
a All 'Stations' in the 'Control tree' are displayed.
3. Press 'Lower level' in an 'Station' list entry.
a All elements of the 'Station' are displayed.
4. Highlight the list entry 'Alarmg. 1'.
a The highlighted list entry is displayed with a bright background.
5. Press 'Execute commands' on the dialog window toolbar.
a The 'Select command' dialog window opens.

Table of Contents

Other manuals for Siemens FT2080

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens FT2080 and is the answer not in the manual?

Siemens FT2080 Specifications

General IconGeneral
BrandSiemens
ModelFT2080
CategoryTouch terminals
LanguageEnglish

Related product manuals