a The 'Select command' dialog window opens.
8. Select the 'RT FIRE channels OFF' command.
a The command execution display confirms successful execution of the
command by displaying .
a The 'RT Fire' is switched off.
a The LED 'Remote alarm Off' on the Person Machine Interface is illuminated.
Switching on the 'RT Fire'
l Proceed as with switching off, but select the 'ON' command.
5.3.5 Switching off alarm activation
WARNING
m parts that have been switched off make it impossible to acquire and
process alarms or faults!
Fire may spread unhindered.
● Deploy staff to monitor the deactivated area.
You must switch deactivated parts of the ↑
' back on as soon as possible.
WARNING! System parts that have been switched off make it impossible to
acquire and process alarms or faults! You can ↑ switch off the fire detection
installation alarm activation for specific elements with this function.
Faults such as the removal of a detector are nevertheless evaluated and displayed.
' command on the following
'XC10 zone'
↑ 'Section'
'Automatic zone'
'Technical zone'
Alarm evaluation OFF
w You are logged onto at least 'Access level' 2.1.
1. Press the button 'Topology' on the GTB.
a The 'Topology' dialog window opens.
2. Press 'Lower level' in the 'Detection tree' list entry.