Issue 07/04  3  Functions 
MICROMASTER 420    Operating Instructions   
6SE6400-5AA00-0BP0 
103 
If the motorized potentiometer is to be used as setpoint source, then either 
parameter P1000 or P0719 should be modified or the BICO parameter r1050 
should be connected to the main setpoint P1070 or supplementary setpoint P1075. 
Contrary to parameter P0719, when parameter P1000 is modified, this implicitly 
changes BICO parameters P1070, P1075.  
Example:  Setpoint via the motorized potentiometer (MOP) 
  a)  Standard method  
→  P1000 = 1 
  b)  BICO method      →  P1070 = 1050 
          P1075 = 0 
The MOP is configured using the following parameters and has the mode of 
operation as shown in Table 3-16: 
 Limits using the minimum frequency P1080 or maximum frequency P1082 
 Ramp-up/ramp-down time P1120 or P1121 
 Inhibits MOP reversing function P1032 
 Saves the MOP setpoint P1031 
 MOP setpoint P1040 
Table 3-16  Mode of operation of the MOP 
Motorized potentiometer 
Lower Raise 
Function 
0  0  Setpoint is frozen 
0 1 Raise setpoint 
1 0 Lower setpoint 
1  1  Setpoint is frozen 
Selecting via BOP or AOP 
The following settings / operator actions should be made when selecting the 
motorized potentiometer using the BOP or AOP: 
Table 3-17  Selecting the motorized potentiometer 
Parameters / keys  BOP  AOP (at the BOP link) 
Command 
source 
P0700 1  4 
P1000 1 
P1035 -  2032.13 (2032.D) 
P1036 -  2032.14 (2032.E) 
 
 
 
 
 
 
 
Raise MOP output frequency 
Setpoint 
source 
 
Lower MOP output frequency