Issue 07/04  5  MICROMASTER 420 specifications 
MICROMASTER 420    Operating Instructions   
6SE6400-5AA00-0BP0 
159 
Table 5-2  Dimensions, required cooling air flow and tightening torques for power terminals 
Frame 
Size 
Dimensions 
Required cooling air 
flow 
Tightening torque for 
power connections 
mm 
73 
× 173 × 149 
l/s 4.8 
Nm 1.1 
A  W x H x D 
inch 
2.87 
× 6.81 × 5.87 
CFM 10.2 
lbf.in  10 
mm 
149 
× 202 × 172 
l/s 24 
Nm 1.5 
B  W x H x D 
inch 
5.87 
× 7.95 × 6.77 
CFM 51 
lbf.in  13.3 
mm 
185 
× 245 × 195 
l/s 54.9 
Nm 2.25 
C  W x H x D 
inch 
7.28 
× 9.65 × 7.68 
CFM 116.3 
lbf.in  20 
 
Table 5-3  Current reduction depending on pulse frequency 
Output current in A with a switching frequency of: Mains voltage  Power (CT) 
[kW] 
4 kHz  6 kHz  8 kHz  10 kHz  12 kHz  14 kHz  16 kHz 
1/3 AC 200 V  0.12 to 5.5   Factory setting 16 kHz – no derating necessary 
0.37  1.2 1.2 1.2 1.2 1.2 1.2 1.1 
0.55  1.6 1.6 1.6 1.6 1.6 1.6 1.1 
0.75  2.1 2.1 2.1 2.1 1.6 1.6 1.1 
1.1  3.0 3.0 2.7 2.7 1.6 1.6 1.1 
1.5  4.0 4.0 2.7 2.7 1.6 1.6 1.1 
2.2  5.9 5.9 5.1 5.1 3.6 3.6 2.6 
3.0  7.7 7.7 5.1 5.1 3.6 3.6 2.6 
4.0  10.2 10.2 6.7 6.7 4.8 4.8 3.6 
5.5  13.2 13.2 13.2 13.2  9.6  9.6  7.5 
7.5  19.0 18.4 13.2 13.2  9.6  9.6  7.5 
3 AC 400 V 
11.0  26.0 26.0 17.9 17.9 13.5 13.5 10.4