3  Functions  Issue 07/04 
  MICROMASTER 420    Operating Instructions 
62  6SE6400-5AA00-0BP0  
By changing the setting of 50/60 Hz DIP switch, after the drive inverter has been 
powered-down/powered-up, the parameters for the rated motor frequency P0310, 
max. frequency P1082 and reference frequency P2000 are automatically pre-set. 
In addition, the rated motor parameters as well as all of the other parameters which 
depend on the rated motor parameters, are reset. The units of the power 
parameters are, depending on P0100, are either interpreted as kW value or hp 
value. 
3.5.2 Quick commissioning 
If there is still no appropriate parameter set for the drive, then a quick 
commissioning must be carried-out including a motor data identification routine. 
The following operator units can be used to carry-out quick commissioning: 
 BOP (option) 
 AOP (option) 
 PC Tools (with commissioning software STARTER, DriveMonitor) 
When the quick commissioning is carried-out, the motor – drive inverter is basically 
commissioned; the following data must be obtained, modified or entered before 
quick commissioning is started:  
 Enter the line supply frequency 
 Enter the rating plate data 
 Command / setpoint sources 
 Min. / max. frequency or ramp-up / ramp-down time 
 Control mode 
 Motor data identification 
Parameterizing the drive with BOP or AOP 
The frequency inverter is adapted to the motor using the quick commissioning 
function and important technological parameters are set. The quick commissioning 
shouldn't be carried-out if the rated motor data saved in the frequency inverter 
(4-pole 1LA Siemens motor, star circuit configuration 
 frequency inverter (FU)-
specific) match the rating plate data. 
Parameters, designated with a * offer more setting possibilities than are actually 
listed here. Refer to the parameter list for additional setting possibilities. 
START
 
 
 
  Factory setting
 
P0003 = 2 
 
 
User access level * 
 1  Standard: Allows access into most frequently used parameters 
  2  Extended: Allows extended access e.g. to inverter I/O functions 
  3  Expert (For expert use only) 
 
P0010 = 1 
 
 
Commissioning parameter * 
 0  Ready 
  1  Quick commissioning  
30 Factory setting 
NOTE 
P0010 should be set to 1 in order to parameterize the data of the motor rating 
plate.
 
0 
1