Issue 07/04 3 Functions
MICROMASTER 420 Operating Instructions
6SE6400-5AA00-0BP0
73
3.5.5.2 Selection of command source
P0700 =...
Selection of
command source
Selects digital command source.
0 Factory fault setting
1 BOP (keypad)
2 Terminal
4 USS on BOP link
5 USS on COM link
6 CB on COM link
P0700 = 2
Sequence control
Setpoint
channel
Motor
control
BOP
USS
BOP link
USS
COM link
Terminals
CB
COM link
3.5.5.3 Digital input (DIN)
P0701=...
Function of digital input 1
Terminal 5
1 ON / OFF1
P0702 =...
Function digital input 2
Terminal 6
12 Reverse
P0703 =...
Function digital input 3
Terminal 7
9 Fault acknowledge
P0704 = 0
Function digital input 4
Via analog input
Terminals 3, 4
0 Digital input disabled
P0724 =...
Debounce time for
digital inputs
Defines debounce time (filtering
time) used for digital inputs.
0 No debounce time
1 2.5 ms debounce time
2 8.2 ms debounce time
3 12.3 ms debounce time
Possible Settings:
0 Digital input disabled
1 ON / OFF1
2 ON + Reverse / OFF1
3 OFF2 – coast to standstill
4 OFF3 – quick ramp-down
9 Fault acknowledge
10 JOG right
11 JOG left
12 Reverse
13 MOP up (increase frequency)
14 MOP down (decrease frequency)
15 Fixed setpoint (Direct selection)
16 Fixed setpoint (Direct selection + ON)
17 Fixed setpoint (Binary coded selection + ON)
21 Local/remote
25 DC brake enable
29 External trip
33 Disable additional freq setpoint
99 Enable BICO parameterization
24 V
T0
&
0 V
Debounce time: DIN
0 ... 3
P0724 (3)
CO/BO: Bin.inp.val
r0722
r0722
Kl.8 P24
Kl.9 0 V
DIN channel
Function of DIN 1
0 ... 99
P0701 (1)
0
99
...
Function
2
1
12
9
0
3